Circuit breaker, ComPacT NSXm 63N, 50kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 40A, EverLink lugs

Rp2.557.573

Deskripsi
Main
Range ComPacT new generation
Product name ComPacT NSXm new generation
Range of product ComPacT NSXm new generation
device short name NSXm 63N
Product or component type Circuit breaker
device application Distribution
Poles description 4P
Protected poles description 3D
Neutral position Left
[In] rated current 40 A 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 90 kA Icu 220…240 V AC 50/60 Hz IEC 60947-2
50 kA Icu 380…415 V AC 50/60 Hz IEC 60947-2
50 kA Icu 440 V AC 50/60 Hz IEC 60947-2
25 kA Icu 500 V AC 50/60 Hz IEC 60947-2
15 kA Icu 525 V AC 50/60 Hz IEC 60947-2
10 kA Icu 660…690 V AC 50/60 Hz IEC 60947-2
Performance level N 50 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 90 kA 220…240 V AC 50/60 Hz IEC 60947-2
50 kA 380…415 V AC 50/60 Hz IEC 60947-2
50 kA 440 V AC 50/60 Hz IEC 60947-2
25 kA 500 V AC 50/60 Hz IEC 60947-2
15 kA 525 V AC 50/60 Hz IEC 60947-2
2,5 kA 660…690 V AC 50/60 Hz IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles 440 V In/2
10000 cycles 440 V In
10000 cycles 690 V In/2
5000 cycles 690 V In
Power dissipation per pole 3,46 W
Mounting support Backplate
Mounting position Horizontal and vertical
Flat on the back
Upside connection Front
downside connection Front
Connection terminals 1 Everlink lug 2,5…95 mm², rigid or stranded aluminium/copper
1 Everlink lug 2,5…70 mm², flexible copper
Connection pitch 35 mm with spreaders
27 mm without spreaders
9 mm pitches 12 module
Trip unit rating 40 A 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7…1 x In
Long-time protection delay adjustment type tr Fixed
Neutral protection settings No protection 3D)
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 600 A
earth-leakage protection Without
Number of slots for electrical auxiliaries 1 auxiliary switch OF
1 alarm switch SD
1 voltage release MN or MX
Local signalling Presence of auxiliary contacts flag green)
Width (W) 108 mm
Height (H) 137 mm
Depth (D) 80 mm
Net weight 1,42 kg
Colour Grey RAL 7016)